Still deciding? Get samples of $ !
Request Sample
|
| Customization: | Available |
|---|---|
| Type: | Isolating Spark Gap |
| Structure: | Monobloc Design |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
|
Type |
ISG 10 |
|
Art.-No. |
6900015 |
|
According to EN 62561-3 / IEC 62561-3 |
Yes |
|
Application |
Earthing Devices for Lightning Equipotential Bonding |
|
Rated DC withstand voltage[Uc] |
350V |
| Rated impulse spark over voltage[Urimp]
|
1000V |
|
Lighting impulse current (10/350µs) |
100kA |
|
Nominal discharge current (8/20µs) [In] |
100kA |
|
Max. discharge current (8/20µs) [Imax] |
200kA |
| 100% lightning impulse sparkover voltage[Uas]
|
≤ 1.5kV |
|
Power frequency sparkover voltage(50Hz)[Uaw] |
≤ 400V |
|
Operating temperature range [Tu] |
-20°C...+60°C |
|
Capacitance at 1MHz [C] |
≤ 400V |
|
Ex certification, according to EN 60079-0 and EN 60079-1:Gas |
Ex db IIC T6 Gb |
|
Ex certification, according to EN 60079-0 and EN 60079-31: Dust |
Ex tb IIIC T80 °C Db IP 66/67 |
|
Insulation resistance at 100V [R] |
≤ 10pF |
|
Length of enclosure |
148mm |
|
Diameter of enclosure |
40mm |
|
Enclosure material |
Orange thermoplastic, UL 94-V0 |
|
Connection via / Connection |
M8 theraded screws / Rd 10 mm |
|
Connection material |
Steel / Cu |
|
Protection level |
IP 66/67 |
|
Certification |
CE (LVD, EMC); RoHS |
|
Compliance |
IEC 61643-21; EN 61643-21; GB 18802.21;EN 62561-3;IEC 62561-3 |


1.Earthing Device according to lEC/EN 62305 in hazardous areas.
2.10mm stainless steel material connection terminal.
3.For mounting in-door or out-door, in damp rooms as well as for underground installation.
4.Extremely loadable unit.
5.Ex marking/IP: Ex db llC T6 Gb, Ex tb lllC T80'C Db IP 66/67.
Summary
1. Used for indirect connnection / earthing of function insulation components during lightning strikes.
2. According to IEC 62305,earting for equipotential connections for lightning strikes in hazardous areas.
3. For lightning equipotential bonding, especially for connection of separated earthing systems.